~V|CONSTRUNARIO|FIEBDC-3/2012|Construnario Versión 3.51||ANSI|||||https://www.construnario.com/bc3/11052/| ~K|\2\2\3\2\2\2\2\EUR\|0| ~C|P28143|u|Circuit breaker RECmax P-D4-20|53451|290124|0| ~T|P28143|The RECmax P series are 2- and 4-pole circuit breakers connected to a compact motor and internal control unit that enables automatic reclosing system. After triggering, the switch reconnects following a sequence of 3 reconnections, with 3 minutes between resets. If the unit is not able to reconnect after 3 attempts, it remains triggered until a manual or remote reset is made. They can also be connected remotely to an external control. It has two inputs that through voltage-free external signals, order the opening (input O) and subsequent closing (reclosing system) of the automatic switch (input I) . They function as protection against shortcircuit and overload, and can also be used as a remote circuit breaker. The switch status is indicated by LED signals on the device’s front panel. An green ON LED indicates that the device is in service; a red OFF LED indicates that the device is triggered. A TEST/RESET of the device can be performed by pressing a button to check the triggering and then reset the device. It also has two single-contact outputs for signalling the status and the cause of the opening and closing of the automatic switch (trigger, manual/Test). Código EAN: 8433059150631| ~F|P28143|0\CMP911_PR1917BI1530_P28143_RECmax_P_D4_20_IMD.jpg\CMP911 PR1917BI1530 P28143 RECmax P D4 20 IMD| ~F|P28143|0\2BC5729BF746BFE018030118D25EBB71.pdf\2BC5729BF746BFE018030118D25EBB71|